Box Fill (314.16) and Conduit Fill (Chapter 9)

Overcrowding a box or a conduit traps heat and makes wire-pulling damage insulation. Two calculations keep things safe: box fill (how much a box must hold) and conduit fill (how many wires fit in a pipe).

1. Box fill — CEC 314.16

You total up "volume allowances" and the box must be at least that big. Each allowance comes from Table 314.16(B), based on conductor size:

ConductorVolume allowance
14 AWG2.00 in³
12 AWG2.25 in³
10 AWG2.50 in³
8 AWG3.00 in³
6 AWG5.00 in³

What counts (and how much):

  • Each current-carrying conductor entering and terminating/splicing in the box = 1 allowance.
  • One or more internal cable clamps = 1 allowance total (based on the largest conductor).
  • Each support fitting (fixture stud, hickey) = 1 allowance each.
  • Each device yoke/strap (switch, receptacle) = 2 allowances (double), based on the largest conductor connected to that device.
  • Equipment grounding conductors: the first four EGCs together = 1 allowance (based on the largest EGC); each EGC beyond four adds ¼ allowance. (For a typical box with ≤4 grounds, that's simply 1 allowance.) (2023 NEC refinement — CEC 314.16(B)(5))

More Planning & Estimating lessons

Browse the full C-10 curriculum or try the practice test.