Capstone: Roughing In a Kitchen Circuit (Integrated Scenario)

This lesson ties Module 2 together the way a real rough-in does: one circuit touches a dozen rules at once. Follow a 20 A, 120 V kitchen small-appliance circuit in a wood-framed dwelling — NM cable to the receptacle boxes, then EMT for an exposed run in the attached garage.

The rules in play

StepRuleValue
Secure the NM near each boxCEC 334.30within 12 in
Size the copper EGC (20 A)CEC Table 250.12212 AWG
Countertop receptacle protectionCEC 210.8(A)GFCI
Kitchen circuit also needs…CEC 210.12AFCI (so: both — dual-function breaker)
NM through a bored hole <1¼ in from edgeCEC 300.4protect with 1/16 in steel plate
Secure the exposed EMT near each boxCEC 358.30within 3 ft
Receptacle ratings on the 20 A circuitCEC 210.21(B)(3)15 A or 20 A
Max breaker on 12 AWG copperCEC 240.4(D)20 A
Wet/damp area (NM not allowed)CEC 334.12switch to EMT/PVC/MC
Wall receptacle spacingCEC 210.52(A)no point > 6 ft from a receptacle