Derating: Bundling Adjustment and Ambient Correction

Table 310.16 ampacities assume ideal conditions (30°C ambient, ≤3 current-carrying conductors). Real installs are often hotter or more crowded, so you "derate" — reduce the allowable ampacity. Two factors do this: bundling adjustment and ambient correction.

1. Bundling adjustment — Table 310.15(C)(1)

When more than three current-carrying conductors run bundled together for more than 24 inches, reduce each conductor's ampacity:

Number of current-carrying conductorsAdjustment
4–680%
7–970%
10–2050%
21–3045%
31–4040%

What counts as "current-carrying":

  • EGC / grounding conductors: never counted. (CEC 310.15(F))
  • Neutral: not counted when it carries only the unbalanced current (e.g., a 3-wire single-phase circuit). It is counted when it carries significant harmonic current from nonlinear loads. (CEC 310.15(E)(1))