Capstone: Trimming Out a Bathroom and an Outdoor Patio (Integrated)

Finish work brings all of Module 3 together. Follow a dwelling bathroom and an outdoor patio trim-out — every device touches several rules.

The rules in play

ItemRuleRequirement
Bathroom receptacle (child safety)CEC 406.12tamper-resistant
Bathroom receptacle protectionCEC 210.8(A)GFCI
Receptacle near basinCEC 210.52(D)within 36 in of the basin's outside edge
Bathroom lighting outletCEC 210.70(A)(1)switched lighting outlet — switched receptacle can't substitute
Outdoor (wet) receptacleCEC 406.9weather-resistant + weatherproof in-use cover
Outdoor receptacle at a dwellingCEC 406.9 + 406.12must be both TR and WR
Metal switch faceplateCEC 406.6connected to the EGC
Every boxCEC 314.25covered (cover/faceplate/canopy)
Replacing an old non-GFCI bath receptacleCEC 406.4(D)(3)must add GFCI (no grandfathering)
Recessed can over shower, in insulationCEC 410.116 + 410.10Type IC and suitably wet/damp-rated

More Finish Wiring & Trim lessons

Browse the full C-10 curriculum or try the practice test.